Overview: Intelligent Multi-sensor Fire Detector

TX7120 Intelligent Multi-sensor Fire Detector has the functions of TX7100 smoke detector and TX7110 heat detector, which makes its application scope wider. Application: Places where the temperature is not high or changes little under normal circumstances, and there is no smoke retention, no large dust, water mist, steam, oil mist pollution, corrosive gas under normal circumstances, and the relative humidity is less than 95%, and the ventilation speed is not more than 5M/second.

Feature and Benefits

•EN54-29 Compliance
•Smoke and Heat analogue sensor and digital communication
•Using microprocessor technology with memory capacity up to 10 events
•Analogue sending and digital addressing
•Provide real time algorithm to the control panel
•Smart linear drift compensation
•360-degree visual indicator
•Onsite Adjustable Parameter
•Removable chamber against dust and small insect
•Ancillary remote indicator output

Technical Specification

Input Voltage: 24VDC [16V to 28V]
Current Consumption: Standby 0.6mA, Alarm:4mA
Protocol/Addressing: T&A, Value range from 1 to 254
Smoke Sensitivity: As per stipulated standard
Heat Class Type: A2R
Indicator: Single LED / 360-degree Visual
Material / Color: ABS / White Glossy finishing
Dimension / Height: Diameter 99.7 mm / 57 mm
Weight: 145g (with Base), 90g (without Base)
Operating Temperature: -10℃ to+50℃
Humidity: 0 to 95% RH, Non condensing

How to Connect TX7120 Smoke Heat Detector?

Please follow picture below to connect these TX7100 optical smoke detector, TX7110 heat detector, TX7120 optical smoke /heat detector. Welcome contact out customer service to get more info.

detector series connection

TX7120 Intelligent Multi-sensor Fire Detector Coverage

The coverage range of TX7120 smoke heat detectors should be used under height 8m, while the radius is 3.6m and scope area is about 20-30 square meters. Summarized in the following table:

heat-scope

TX7 Serials Addressable Fire Alarm Panels System

The Fire Alarm Panel System is a powerful system that not only requires a core control panel like the LPCB-certified TX7004 FACP Fire Alarm Control Panel, but also needs to be paired with other detectors, modules, and appropriate configurations based on the project’s scale to maximize its effectiveness.