6 Types of Fire Alarm Control Panel (FACP) Connections | Fire Alarm System Control Panel Guide

In the hardware connection and data exchange of the Fire Alarm Control Panel (FACP), USB Type-B, Ethernet, CanBus, Serial RS232 & 485, and Modbus (Note: Modbus is a communication protocol that relies on a physical interface and is often combined with RS232/485 and Ethernet) are suitable for different scenarios due to their different technical characteristics.

 

Their core features can be analyzed in terms of communication distance, speed, stability, scalability, and adaptability to firefighting scenarios for residential, commercial, and industrial environments. They enable timely fire detection, alarm, and activation of firefighting equipment (such as sprinklers, smoke exhaust fans, and fire doors) via the fire alarm system control panel. This not only provides timely assistance for escape, but also quickly provides firefighters with the fire location, saving rescue time and protecting lives and property.

USB-B-Ethernet-CanBus-SerialRS232-rs485-modbus

1. USB Type-B Connection:

USB Type-B is the core interface for local debugging and data backup in the control panel (specifically the Fire Alarm Control Panel (FACP)). It is primarily used for on-site operation by engineers rather than long-term online communication.

1.1. Extremely Short Communication Distance:

Standard USB 2.0/3.0 cables are only 5 meters long, making them inadequate for long-distance connections between fire protection system devices (e.g., between floors or buildings). They only support close-range interaction between the control panel and a local computer/debugging device.

1.2. High Stability (Local Scenario):

Direct point-to-point connection eliminates network interference, making it suitable for on-site configuration of parameters (e.g., alarm thresholds, device addresses), firmware upgrades, and fault data export.

1.3. Limitations in Fire Protection Scenario:

USB is designed for local maintenance only and cannot support remote monitoring (e.g., fire control room management of remote buildings). USB also cannot connect to on-site detectors (e.g., smoke and temperature sensors) that transmit data to the FACP.

TX7004-fire-alarm-control-panel-technical-inside

2. Ethernet Connection:

Ethernet is the mainstream method for remote networking and centralized monitoring of fire protection systems, connecting Fire Alarm Control Panel (FACP) units across areas. It relies on the TCP/IP protocol to enable multi-device, cross-regional communication, and the most common connector is the RJ45.

2.1. Long communication distance (requires auxiliary equipment):

A single network cable (CAT5e/CAT6) can reach up to 100 meters. Combined with switches and routers, it enables cross-building (e.g., several kilometers via fiber optic cable) and cross-city connections, meeting the networking needs of large campuses and urban fire protection systems.

2.2. Strong scalability:

Supports star topology, enabling flexible integration of multiple subsystems (such as fire alarms, sprinkler control, and emergency lighting). Adding new equipment requires only connecting to a switch, eliminating the need for network reconstruction.

2.3. Firefighting Scenarios:

Suitable for centralized monitoring: The fire control room can view the status of all substation fire alarm control panel facp units in real time via Ethernet and remotely issue commands (such as resetting faulty equipment).

TX7004-fire-alarm-control-panel-technical-Loop-Capacity-Modularity

3. CANBus (Controller Area Network) Connection:

The CANBus interface can be used for both short-range communication between the fire alarm control panel and field devices, as well as for communication between multiple fire control panels, such as connecting devices on the same floor or between buildings.

3.1. Moderate communication distance:

Up to 1000 meters without a repeater, covering connections within a single building (e.g., floors 1-10) or within a control room (e.g., control panel with local audible and visual alarms, manual call points). When used with a fiber optic converter, the transmission distance is significantly increased to 15 km, enabling interoperability across multiple buildings.

3.2. Highly resistant to interference:

Can withstand electromagnetic interference in industrial environments (e.g., electromagnetic radiation from motors and distribution cabinets), preventing false alarms or loss of fire signals—critical requirements for fire protection systems (false alarms can trigger unnecessary evacuations, while signal loss can delay fire response).

3.3. Fire scenario adaptability:

Suitable for field equipment networking: Networking units can reach up to 99 sets, eliminating the need for complex wiring (only two wires are required), reducing construction costs.
Supports fault self-detection: The CANbus protocol includes a built-in error detection mechanism that identifies faults such as disconnections and device offline in real time and reports them to the control panel, facilitating rapid troubleshooting by engineers. (For example, if a smoke detector on a certain floor goes offline, the system will immediately display a message stating “Device fault at address XX”).

4. Serial RS232 & RS485 Connections:

RS232 and RS485 are point-to-point/point-to-multipoint serial communication interfaces in traditional fire protection systems. Both are physical layer standards and are often used with protocols such as Modbus and ASCII to connect fire alarm control panels. Their core differences lie in communication distance and topology.

Tanda fire alarm system

5. Modbus Connection (Communication Protocol, Implemented via a Physical Interface):

Modbus is not a standalone physical interface, but rather an application layer communication protocol commonly used in fire protection systems. It relies on RS232, RS485 (known as Modbus RTU), or Ethernet (known as Modbus TCP/IP) for data exchange. Its core function is to unify the communication “language” of different devices in fire alarm system control panel ecosystems.

5.1. Simple Protocol, Strong Compatibility:

The Modbus protocol frame structure is simple (for example, an RTU frame contains only an address code, function code, data, and a checksum). This allows for interconnection between control panels, detectors, and third-party devices (such as building automation systems), avoiding “protocol silos.”

5.2. Two mainstream forms:

Modbus RTU (based on RS485): Suitable for short-range, low-cost networking on-site (e.g., communication between a control panel and modules on ten floors). It offers strong interference resistance and is suitable for real-time data transmission (e.g., module status, alarm signals) between fire terminal equipment.
Modbus TCP/IP (based on Ethernet): Suitable for remote networking (e.g., communication between a fire control room and remote substations or cloud platforms). Based on the TCP/IP protocol, it enables cross-regional monitoring over the internet and supports concurrent transmission of large amounts of data (e.g., summary of device status across the entire network).

5.3. Fire scenario adaptability:

The BMS (Building Management System) is the core platform for centralized monitoring, coordinated control, and energy efficiency management of building equipment. Modbus, a mature open-source communication protocol in the industrial field, serves as a critical bridge for data interoperability and collaborative control between the BMS and the fire alarm control panel. The key to this coordination is that when the FACP detects a fire and transmits a “fire alarm signal” to the BMS via Modbus, the BMS immediately suspends its normal control logic and coordinates non-firefighting equipment to assist with fire rescue efforts. For example, this involves shutting off the power to the air conditioner unit, activating emergency lighting on the fire floor and evacuation corridors, and automatically unlocking access control systems on the fire floor and evacuation corridors. This ultimately improves overall building safety and operational efficiency.

5.4. Supports "read-write separation":

The control panel can obtain terminal device status (such as reading smoke alarm signals) through Modbus “read commands” and issue control commands (such as writing commands to activate sprinkler modules) through “write commands.” This provides clear logic and facilitates system debugging and maintenance.

Fire Control Panel Connection Methods (English Version)
Connection Method Core Purpose Advantageous Scenarios Typical Application Case
USB Type-B Local Debugging & Data Backup On-site engineer operations (configuration, firmware update, log export) On-site programming connect FACP to a laptop to import new firmware
Ethernet Remote Networking & Centralized Monitoring Large-scale parks, cross-building fire protection networking Fire control room monitors sub-stations in 99 buildings via Ethernet
CanBus On-site Device (Short-distance) Networking Device interconnection within the same floor/control room FACP connects 512 smoke detectors sounder strobe alarms or interlink between TX7004
RS232 Local Point-to-Point Communication FACP connected to a single local device (e.g., printer) FACP connects to Graphic Monitor Center Software, normally support distance within 10 meters
RS485 (Modbus RTU) On-site Point-to-Multipoint Communication (Low Cost) Multi-module interconnection in small-scale systems FACP connects to Graphic Monitor Center Software, or support Modbus RTU
Modbus TCP/IP Remote Multi-Device Interconnection (Standardized) Cross-brand, cross-region device collaboration FACP connect to BMS (Building Management System)

Note: Fire control panels typically use a combined connection solution to leverage the advantages of different methods, ensuring stable and reliable system operation.

In summary, the connection method for a control panel (especially the Fire Alarm Control Panel (FACP)) should be selected based on distance, number of devices, real-time performance, and interference resistance requirements. A typical solution is a combination of Ethernet (remote networking) + CanBus/RS485 (on-site networking) + USB Type-B (local maintenance), supplemented by the Modbus protocol to ensure device compatibility and stable, reliable operation.

Recommaned Products

FAQ

What is a Fire Alarm Control Panel (FACP)?

A Fire Alarm Control Panel (FACP) is the central hub of a fire alarm system that monitors inputs and controls outputs to alert occupants in case of fire.

The six main types of FACP connections are USB Type-B, Ethernet, CANBus, RS232, RS485, and Modbus.

Ethernet and RS485 are commonly recommended for building fire alarm systems because they support longer distances, scalability, and stable communication.

Yes. A common solution is combining Ethernet for centralized monitoring, RS485 or CANBus for on-site networking, and USB for local maintenance, with Modbus protocol ensuring system compatibility.