TX7200 Addressable Input Module
40+ years
Experience
400+ Patents
Full sets LPCB
1,000,000+
projects worldwide
Global on site
after sale service
7x24h
response service

Overview: TX7200 Addressable Input Module
The TX7200 Addressable Input Module is used to monitor the action status information of on-site active fire-fighting equipment and feed back the information to the alarm controller. Common active equipment – water flow indicator, signal butterfly valve, pressure switch, 70℃ fire damper.
The linkage control device is the link connecting the on-site linkage equipment. Through the linkage control device, the status information of the on-site linkage equipment can be monitored, and the start and stop of the on-site linkage equipment can be controlled.
Menu
Feature and Benefits
•EN54-18 Compliance
•Built-in MCU processor and digital addressing
•Fire or Supervisory signal configuration
•Input cable monitored
•Normally open configuration
•LED status indicator
•Loop powered device
•Surface mounting with fix base for simple installation
Technical Specification
Input Voltage: 24VDC [16V to 28V]
Current Consumption: Standby 0.7mA, Alarm: 1.2mA
Protocol/Addressing: T&A, Value range from 1 to 254
Input Relay: Normally Open dry contact
Input Resistance: 5.1Kohms/ ¼ W
Indicator Status: Normal: Single blink/Active: Steady/Fault: Double Blink
Material / Color: ABS / White Glossy finishing
Dimension / LWH: 108 x 86 x38 mm
Weight: 155g (with Base), 85g (without Base)
Operating Temperature: -10℃ to +50℃
Ingress Protection Rating: IP30
Humidity: 0 to 95% RH, Non condensing
TX7 Serials Addressable Fire Alarm Panels
A Fire Alarm System is powerful that not only requires a core control panel like the LPCB CE certified TX7004 FACP (Fire Alarm Control Panel), but also needs to be paired with other detectors, modules, and appropriate configurations based on the project’s scale to maximize its effectiveness.